SCHOTT® Pyran® Fire-Protective Glass Ceramic

Discover SCHOTT PYRAN® Platinum fire-rated glass-ceramic glazing. Industry-leading, UL-certified fire protection and impact safety with no amber tint for commercial projects.

Advanced Fire-Rated Glass-Ceramic for Modern Architecture

As a trusted supplier of architectural fire-rated glass in North America, we are proud to offer the SCHOTT PYRAN® Platinum product line—the world’s first and only floated glass-ceramic designed specifically for demanding architectural applications. This advanced, transparent, and wireless glazing is manufactured using an innovative micro-float process, delivering a smooth, distortion-free surface and the industry’s largest sheet sizes up to 51″ x 99″.

Providing 90 to 180 minutes of fire and thermal shock protection, it successfully passes rigorous positive pressure (UL 10C) and hose-stream tests to effectively prevent the spread of fire, smoke, and hot gases. Unlike traditional materials, it delivers an exceptionally clear, neutral gray tone completely free of amber tinting that matches standard architectural float glass.

The PYRAN® line is available in stock or cut-to-size formats, including standard monolithic, filmed (Platinum F), and laminated (Platinum L) configurations that satisfy both ANSI Z97.1 and CPSC 16 CFR 1201 impact safety standards. Whether your project involves educational facilities, healthcare centers, or commercial hubs, this versatile and eco-friendly solution can be constructed into insulated glazing units (IGUs) or customized with opacity, allowing architects and contractors to achieve open, modern aesthetics without compromising on safety or sustainability for their next project.

Icon Target Environment Icon Key Threat Mitigation Icon Visual Goal

Educational Facilities: Classrooms, Hallways, & Stairwells

Impact Safety & Fire Containment: Protection from fire, hot gases, smoke, and impact up to 180 minutes.

Natural Light & Clarity: Neutral gray tone with no amber tint; high light transmission (~80%) for student wellness.

Healthcare & Wellness Centers: Corridors & Wards

Thermal & Pressure Resistance: Meets UL 10C positive pressure testing; high viscosity maintains structural integrity under thermal loads.

Calm Environment: High optical and float-glass-quality surface that provides clear, distortion-free views.

Commercial Offices & Retail Hubs: Atriums & Storefronts

Corridor & Exit Protection: Fire-protective glazing for life safety along standard building exit routes.

Modern Aesthetics: Largest available sheet sizes in the industry (up to 51″ x 99″) for seamless, open architectural designs.

Government & Justice Centers Secure Partitions)

Multi-Hazard Resistance: PYRAN Platinum L & F offer impact safety (ANSI Z97.1 / CPSC 16CFR1201) and fire protection up to 3 hours.

Clear Sightlines: True-color rendition for staff awareness and monitoring, with options for opacity films.

Hospitality & Transportation Hubs Lobbies & Terminals

High-Traffic Durability: Withstands rigorous hose stream tests and thermal shock.

Welcoming Ambience: Environmentally friendly and heavy metal-free glass-ceramic that matches regular float glass in appearance.

Attributes
  • Fire
  • Products F/L Impact-Safety
  • Hose-Stream
  • Security Options
  • No Amber Tint
  • Framing Options
  • UL Listed
  • LEED

SCHOTT PYRAN® Resources

View by Category
  • BIM files
  • Brochures
  • Datasheets
View all Resources

Technical Data

SCHOTT PYRAN® can be used to construct insulated glazing units and can be lightly delivered with surface-applied opacity film, without affecting fire rating.

Product Name Thickness Weight Impact-Safety Rated Performance Standards

SCHOTT PYRAN® Platinum

3/16″

2.5 lbs/ft²

No

UL 9, UL 10B, UL 10C, UBC 7-2 (1997), UBC 7-4 (1997), NFPA 80, NFPA 252, NFPA 257, CAN/ULC S104, CAN/ULC S106, ANSI Z97.1, CPSC 16CFR1201

SCHOTT PYRAN® Platinum F

3/16″

2.5 lbs/ft²

Yes

UL 9, UL 10B, UL 10C, UBC 7-2 (1997), UBC 7-4 (1997), NFPA 80, NFPA 252, NFPA 257, CAN/ULC S104, CAN/ULC S106, ANSI Z97.1, CPSC 16CFR1201

SCHOTT PYRAN® Platinum L

3/16″

2.5 lbs/ft²

Yes

UL 9, UL 10B, UL 10C, UBC 7-2 (1997), UBC 7-4 (1997), NFPA 80, NFPA 252, NFPA 257, CAN/ULC S104, CAN/ULC S106, ANSI Z97.1, CPSC 16CFR1201

Listed Sizing Per Application

Product Name Fire-Rating Applications Temp-Rise
Performance
Hose-Stream
Test
Impact-Safety
Rated
Building Code Marking

SCHOTT PYRAN®

Platinum

up to 90 Minutes

Transom lites, sidelites, windows

No

Pass

No

OH-90

SCHOTT PYRAN®

Platinum F

up to 90 Minutes

Doors
non-temp-rise

No

Pass

Yes

D-H-90

SCHOTT PYRAN®

Platinum F

up to 90 Minutes

Other than Doors

No

Pass

Yes

OH-90

SCHOTT PYRAN®

Platinum F

up to 180 Minutes

Doors
temp-rise and non-temp-rise

No

Pass

Yes

D-H-180

SCHOTT PYRAN®

Platinum L

up to 90 Minutes

Transom lites, sidelites, windows

No

Pass

Yes

OH-90

SCHOTT PYRAN®

Platinum L

up to 90 Minutes

Doors
non-temp-rise

No

Pass

Yes

D-H-90

SCHOTT PYRAN®

Platinum L

up to 180 Minutes

Doors
temp-rise and non-temp-rise

No

Pass

Yes

D-H-180

Listings & Test References

UL
  • UL 9
  • UL 10B
  • UL 10C
UBC
  • UBC 7-2 (1997)
  • UBC 7-4 (1997)
NFPA
  • NFPA 80
  • NFPA 252
  • NFPA 257
ASTM
  • ASTM E2010-01
  • ASTM E2074-00
CAN/ULC
  • CAN/ULC S104
  • CAN/ULC S106
ANSI
  • ANSI Z97.1
CPSC
  • 16 CFR 1201
Product Certification Testing References
  • ASTM E2074-00: Standard Test Method for Fire Tests of Door Assemblies
  • NFPA 80: Requires that fire doors be inspected and tested immediately after the initial installation and then at a minimum annually after that.
  • NFPA 252: Standard Methods of Fire Tests of Door Assemblies
  • NFPA 257: Standard on Fire Test for Window and Glass Block Assemblies
  • ASTM E2074-01: Standard Test Method for Positive Pressure Fire Tests of Window Assemblies
  • CAN/ULC S104: Standard Method for Fire Tests of Door Assemblies
  • CAN/ULC S106: Standard Method for Fire Tests of Window and Glass Block Assemblies
  • ANSI Z97.1 and CPSC 16 CFR 1201 Cat I and Cat II (Category I and/or Category II) Safety- Impact performance criteria

Smooth, clear, float-glass.

Our dedicated team of experienced industry veterans offers end-to-end project support, from start to finish. We know the products, and we know the codes. When you partner with McGrory, we make sure the right glazing is used in the proper application

Watch our testing in action

Ready to move forward?